Power Analyzer PCE-830-2 in Pakistan

Power Analyzer PCE-830-2 in Pakistan

  • Rs.0



PCE-830-2 Power Analyzer with 3 phases / Measures power and analyses harmonics / Includes memory, interface, and software.

Specification:

Technical Specifications
Measurement valuesMeasurement ranges / resolution / accuracy
PCE-830 + PCE-6801
Watts AC (50 Hz or 60 Hz, PF 0.5 up to 1)
5.0 W to 999.9 W / 0.1 W / ±1% ±0.8 W
1.000 kW to 9.999 kW / 0.001 kW / ±1% ±8 W
10.00 kW to 99.99 kW / 0.01 kW / ±1% ±80 W
100.0 kW to 999.9 kW / 0.1 kW / ±1% ±0.8 kW
1,000 kW to 9,999 kW / 1 kW / ±1% ±8 kW
PCE-830 + PCE-6802
Watts AC (50 Hz or 60 Hz, PF 0.5 up to 1)
5.0 W to 999.9 W / 0.1 W / ±1% ±0.8 W
1.000 kW to 9.999 kW / 0.001 kW / ±1% ±8 W
10.00 kW to 99.99 kW / 0.01 kW / ±1% ±80 W
100.0 kW to 999.9 kW / 0.1 kW / ±1% ±0.8 kW
1000 kW to 9999 kW / 1 kW / ±1% ±8 kW
0.000 MW to 9.999 MW / 0.001 MW / ±1% ±80 kW
PCE-830 + PCE-3007
Watts AC (50 Hz or 60 Hz, PF 0.5 up to 1)
10.0 W to 999.9 W / 0.1 W / ±1% of measurement range
1.000 kW to 9.999 kW / 0.001 kW / ±1% of measurement range
10.00 kW to 99.99 kW / 0.01 kW / ±1% of measurement range
100.0 kW to 999.9 kW / 0.1 kW / ±1% of measurement range
1,000 kW to 9,999 kW / 1 kW / ±1% of measurement range
PCE-830 + PCE-6801
Current AC (50 Hz or 60 Hz, auto range select, TRMS)
0.04 A to 1 A / 0.001 A / ±0.5% ±0.05 A
0.4 A to 10.0 A / 0.01 A / ±0.5% ±0.05 A
4 A to 100.0 A / 0.1 A / ±1.0% ±0.5 A
PCE-830 + PCE-6802
Current AC (50 Hz or 60 Hz, auto range select, TRMS)
10.00 A / 0.01 A /
4 A to 100.0 A / 0.01 A / ±0.5% ±0.5 A
40 A to 1000.0 A / 0.1 A / ±0.5% ±5 A
PCE-830 + PCE-3007
Current AC (50 Hz or 60 Hz, auto range select, TRMS)
0 to 300 A / 0.1 A / ±1.0% of measurement range
300.0 A to 999.9 A / 0.1 A / ±1.0% of measurement range
1,000 A to 3,000 A / 1 A / ±1.0% of measurement range
Voltage AC (50 Hz or 60 Hz, TRMS)20.0 V ... 500.0 V / 0.1 V / ±0.5 % ±5 digits
(grounded)
20.0 V ... 600.0 V / 0.1 V / ±0.5 % ±5 digits
(phase to phase)
Harmonic distortionof AC voltage1º to 20º / 0.1% / ±1.0%
21º to 49º / 0.1% / 4% of reading ±2.0%
50º to 99º / 0.1% / 6% of reading ±2.0%
PCE-830 + PCE-6801
Harmonics of AC current in %
1º to 20º / 0.1% / ±0.2% of reading ±1.0%
11º to 20º / 0.1% / ±2% of reading ±1.0%
21º to 50º (A)/ 0.1% / ±5% of reading ±1.0%
21º to 50º (mA)/ 0.1% / ±10% of reading ±1.0%
51º to 99º / 0.1% / ±35% of reading ±1.0%
PCE-830 + PCE-6802
Harmonics of AC current in %
1º to 10º / 0.1% / ±2%
21º to 49º / 0.1% / 4% of reading ±2.0%
50º to 99º / 0.1% / 6% of reading ±2.0%
PCE-830 + PCE-3007
Harmonics
 of AC current in %
1º to 10º / 0.1% / ±2%
21º to 49º / 0.1% / ±6%
50º to 99º / 0.1% / ±10%
PCE-830 + PCE-6801 / PCE-830 + PCE-6802
Power Factor (PF)
0.00 to 1.00 / 0.01 / ±0.04
PCE-830 + PCE-3007
Power Factor (PF)
0.000 to 1,000 / 0.001 / ±0.04
PCE-830 + PCE-6801 / PCE-830 + PCE-6802
Phase angle (Phi)
-180° to 180° / 0.1° / ±1°
PCE-830 + PCE-3007
Phase angle (Phi)
0° to 180° / 0.1° / ±2°
PCE-830 + PCE-6801
Total harmonic distortion
0.0 to 20.0% / 0.1% / ±1%
20.0% to 100% / 0.1% / ±3% of reading ±5%
100% to 999.9% / 0.1% / ±10% of reading ±10%
PCE-830 + PCE-6802
Total harmonic distortion
0.0 to 20.0% / 0.1% / ±2%
20.0% to 100% / 0.1% / ±6% of reading ±1%
100% to 999.9% / 0.1% / ±10% of reading ±1%
PCE-830 + PCE-3007
Total harmonic distortion
0.0 to 20.0% / 0.1% / ±2%
20.0% to 100% / 0.1% / ±6% of reading ±1%
100% to 999.9% / 0.1% / ±10% of reading ±1%
Maximum measurement of AC voltage and current50 Hz / 19 µS / ±5% ±30 digits
60 Hz / 16 µS / ±5% ±30 digits
Peak value measurement of AC voltage and current1.00 to 99.99 / 0.01 / ±5% ±30 digits
Frequency range in automatic mode45 Hz to 65 Hz / 0.1 H z / 0.1 Hz
Memory512 kB for a maximum 52,420 readings taken by 1 phase / 2 conductors
PortUSB
Software and cableincluded, for Windows 2000, XP, ME
Displaybacklit LCD with dot matrix
Power8 AA batteries (Mignon)
Dimensions257 mm x 155 mm x 57 mm
10.1 in x 6.10 in x 2.24 in
Weight1.16 kg / 2.56 lbs
Operating conditionsmax. 85% relative humidity
-10º C to 50º C / 14º F to 122º F
Type of protection / standardsIEC 61010, 600 V/CAT III
Set 1:
PCE-830 + PCE-6801 amp clamp (100 A)

- Electrical conductor pick-up: 30 mm / 1.2 in diameter
- Range selection: manual (1 A, 10 A, 100 A)
- Dimensions: 210 mm x 62 mm x 36 mm / 8.2 in x 2.4 in x 1.4 in
- Weight: 200 g / 7 oz
Set 2:
PCE-830 + PCE-6802 amp clamp (1000 A)

- Electrical conductor pick-up: 55 mm / 2.2 in diameter
- Range selection: manual (10 A, 100 A, 1,000 A)
- Dimensions: 244 mm x 97 mm x 46 mm / 8.6 in x 97 in x 46 in
- Weight: 600 g / 1.3 lbs
Set 3:
PCE-830 + PCE-3007 flexible amp clamp (3000 A)
- Electrical conductor pick-up: 170 mm / 6.69 in diameter
- Minimum radial curve : 35 mm / 1.4 in
- Length of electrical conductor: 610 mm / 24.0 in
- Diameter of electrical conductor: 14 mm / 0.55 in
- Dimensions (Box): 130 mm x 80 mm x 43 mm / 5.1 in x 3.1 in x 1.6 in
- Weight: 410 g / 14.4 oz
Outline of the PCE-830
Connecting the amp clamps to the PCE-830:
1. Turn on the device.
2. Push the "1f3f" key until "3P3W" appears on the display for 3 phases / 3 conductors.
3. Connect the 3 test cables from the voltage with L1, L2, L3 and the analyser. The amp clamps are connected, as seen in the image to the right, between the device and the circuit.
4. The results can then be seen on the display.

Delivery Scope:

1 x PCE-830-2 Power Analyzer
3 x Amp clamps - Depending on set ordered (PCE-6801, PCE-6802, or PCE-3007)
4 x Alligator clips
4 x Safety test lines (3 m / 3.3 ft long)
8 x Batteries
1 x Mains adaptor
1 x Carrying case
1 x USB cable software
1 x User's manual


Download the Manual of PCE-830-2

Download the Data Sheet of PCE-830-2 

Tags: Power Analyzer, Power Analyzer in Pakistan,