Current Clamp PCE-CM 5 in Pakistan

Current Clamp PCE-CM 5 in Pakistan

  • Rs.0



Digital multimeter with NCV measurement / Current measurement up to 200 A AC / Frequency measurement directly at the current clamp / Ready for immediate use / Simple operation.

Specification:

Alternating current 
Measuring rangeResolutionAccuracy
200 A0.1 A± (3.0% + 3 digits)
Frequency range: 40 ... 400 Hz
Maximum input current: 200 A AC
  

 
Direct current 
Measuring rangeResolutionAccuracy
600 µA0.1 µA± (1.0% + 4 digits)
1000 µA1 µA± (1.0% + 4 digits)
Maximum input current: 1000 µA
  

 
DC 
Measuring rangeResolutionAccuracy
600 mV0.1 mV± (0.7% + 3 digits)
6V0.001 V± (0.7% + 3 digits)
60V0.01 V± (0.7% + 3 digits)
600V0.1 V± (0.7% + 3 digits)
Input impedance: 10 MΩ
maximum input voltage: 600V DC AC rms
   

 
AC 
Measuring rangeResolutionAccuracy
6V0.001V± (0.8% + 3 digits)
60V0.01V± (0.8% + 3 digits)
600V0.1V± (0.8% + 3 digits)
Input impedance: 10 MΩ
Maximum input voltage: 600V DC AC rms
Frequency range: 40 ... 400 Hz
 

 
LowZ AC / DC 
Measuring rangeResolution   Accuracy
600V0.1V± (2.0% + 3 digits)
Input impedance: 10 MΩ
Maximum input voltage: 600V DC AC rmsS
Frequency range: 40 ... 400 Hz
   

 
Resistance 
Measuring rangeResolutionAccuracy
600 Ω0.1 Ω± (0.8% + 3 digits)
6 kΩ0.001 kΩ± (0.8% + 3 digits)
60 kΩ0.01 kΩ± (0.8% + 3 digits)
600 kΩ0.1 kΩ± (0.8% + 3 digits)
6 MΩ0.001 MΩ± (1.2% + 3 digits)
60 MΩ0.1 MΩ± (1.2% + 3 digits)
Test voltage (open circuit): 0.4V
Surge protection: 250V AC / DC rms
 

 
Continuity test 
Measuring rangeResolutionaccuracy
-0.1 Ω-
Surge protection: 250 V AC / DC rms
Beep at <50 Ω
   

 
Diode test 
Measuring rangeResolutionAccuracy
-0.001V-
Surge protection: 250V AC / DC rms
Forward current: 1-mA DC
Forward voltage: 3.3V DC
   

 
Capacities 
Measuring rangeResolutionAccuracy
99.99 nF0.01 nF± (4.0% + 5 digits)
999.9 nF0.1 nF± (4.0% + 5 digits)
9.999 µF0.001 µF± (4.0% + 5 digits)
99.99 µF0.01 µF± (4.0% + 5 digits)
999.9 µF0.1 µF± (4.0% + 5 digits)
9.999 mF1 µF± (4.0% + 5 digits)
99.99 mF0.01 mF± (4.0% + 5 digits)
Surge protection: 250V AC / DC rms
   

 
Temperature (thermocouple type K) 
Measuring rangeResolutionAccuracy
-20 ... 0°C1°C± (3.0% + 2 digits)
1 ... 400°C1°C± (2.0% + 2 digits)
-4 ... 32°F1°F± (3.0% + 4 digits)
33 ... 752°F1°F± (2.0% + 4 digits)
Surge protection: 250V AC / DC rms
   

 
Frequency (with current probe) 
Measuring rangeResolutionAccuracy
99.99 Hz0.01 Hz
± (1.5% + 5 digits)
999.9 Hz0.1 Hz± (1.5% + 5 digits)
> 1 kHz0.001 kHzfor reference only
Frequency range: 10 Hz ... 1 kHz
Maximum input current: 200 A AC rms
Input range: > 60 A AC rms (if the input current increases, the frequency also increases)
   

 
Frequency (when measuring voltage) 
Measuring rangeResolutionAccuracy
99.99 Hz0.01 Hz± (1.5% + 5 digits)
999.9 Hz0.1 Hz± (1.5% + 5 digits)
9.999 Hz0.001 kHz± (1.5% + 5 digits)
> 10 kHz0.01 kHzfor reference only
Frequency range: 10 Hz ... 10 kHz
   

 
Frequency (direct measurement) 
Measuring rangeResolutionAccuracy
99.99 Hz0.01 Hz± (0.3% + 5 digits)
999.9 Hz0.1 Hz± (0.3% + 5 digits)
9.999 Hz1 Hz± (0.3% + 5 digits)
99.99 kHz0.01 kHz± (0.3% + 5 digits)
999.9 kHz0.1 kHz± (0.3% + 5 digits)
9.999 kHz1 kHz± (0.3% + 5 digits)
99.99 MHz0.01 MHz± (0.3% + 5 digits)
   
Measuring range: 10 Hz ... 60 MHz
Input impedance: 10 MΩ
Input range:> 0.2V AC rms (the input voltage increases, the frequency also increases)
Maximum input voltage: 250V AC rms
 

 
Duty cycle 
Measuring rangeResolutionAccuracy
5 ... 95%0.1%± 0.3%
   
More specifications 
Range selectionAutomatically and manually
Maximum working height2000 m / 6561.7 ft
DisplayLCD display
Largest display value5999
Overrange"OL" display
Measuring range underflow"-OL" display
Measuring rate3 measurements per second
Automatic shutdownAfter 15 minutes of inactivity
Power supply1 x 9V block battery
Operating conditions0 ... 40°C / 32 ... 104°F
Storage conditions-10 ... 50°C / 14 ... 122°F
Dimensions201 x 65 x 43 mm / 7.9 x 2.6 x 1.7 in
WeightApprox. 265 g / < 1 lb (with battery)


Delivery Scope:

&l

Tags: Current Clamp, Current Clamp in Pakistan,